Adjust 20% overcapacity for panelscheme - E-Schema


Last modified on: 9. Juli 2020

Problem:

When you create/generate a panelscheme for a Electrical panel the total load gets a 20% increase.
This is not desired. How can this value be adjusted?

 

Solution:

  • Open Windows Explorer
  • Browse to the folder: C:\Users\<gebruiker>\AppData\Roaming\Cadac Group\Techniek 10.x\ES\I\
  • Select the eschema.ini
  • Open it with Notepad
  • Locate the header [TOTBOX]
  • Adjust the line PROCENT=20 to PROCENT=0 (or any desired value)
  • Save the eschema.ini.

  • Update the scheme.